Final | 3/31/2015 | 4/1/2015 | 4/1/2015 | A | PASS |
Bob Reichert
|
|
|
Keith Phone #: ###-#### ok final
|
Final | 3/27/2015 | 3/27/2015 | 3/27/2015 | P | FAIL |
Bob Reichert
|
|
|
Keith-if locked call Keith for access Phone #: ###-#### called, left correction notice, BCC shall change room count from 1 to 10 rooms on permit, NEC 110.26(E) there shall be no foreign systems in dedicated panel space i.e. ducts or piping, 334.30 shall securely support nm cable within 12" of panel, 300.4 shall provide cable protection if over 1/14" to edge of hole or cable
|
Electrical Rough-In | 1/21/2015 | 1/21/2015 | 1/21/2015 | P | PASS |
Cevyn Recla
|
|
|
Keith Phone #: ###-#### RI OK, upstairs cut in and rewired, basement was all open and wired
|
Conference | 11/12/2014 | 11/13/2014 | 11/13/2014 | A | DONE |
Bob Reichert
|
|
|
Please call ahead for access, coming from Nampa - Keith Phone #: ###-#### talked about remodel of old house, knob and tube replacement, how far to go for upgrade
|