Final | 1/9/2015 | 1/12/2015 | 1/12/2015 | A | PASS |
Cevyn Recla
|
|
|
If locked please call for garage code, thanks Phone #: ###-#### Inspection requested via web by Robert Schroder corrections made, Final OK
|
Final | 1/9/2015 | 1/9/2015 | 1/9/2015 | P | FAIL |
Cevyn Recla
|
|
|
If house is locked please call for garage code, thank you. Also if in near vicinity ready now. Phone #: ###-#### Inspection requested via web by Robert Schroder 210.4 B multiwire branch circuit shall be provided with means to disconnect all ungrounded conductors simultaneously 314.20 boxes shall be not be set back more than 1/4 inch of finished surface 200.7 C 1 insulation shall be permanently reidentified to indicate its use as an ungrounded conductor at all visible locations called contracor
|
Final | 11/19/2014 | 11/19/2014 | 11/19/2014 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder see rip
|
Rough-In Permanent Service | 11/19/2014 | 11/19/2014 | 11/19/2014 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder ri ok, p/s o/h n ok
|
Electrical Rough-In | 11/12/2014 | 11/13/2014 | 11/13/2014 | A | PASS |
Bob Reichert
|
|
|
Inspect can lights in soffit for cover Phone #: ###-#### Inspection requested via web by Robert Schroder soffits only ok cover
|