Final | 1/27/2015 | 1/27/2015 | 1/27/2015 | P | PASS |
Rex Boyles
|
|
|
final ok
|
Final | 1/26/2015 | 1/27/2015 | 1/27/2015 | A | CANC |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk
|
Final | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | FAIL |
Rex Boyles
|
|
|
Garage code 1979E Phone #: ###-#### Inspection requested via web by Alan Lusk 210.12(A)(1)-AFCI protection required in dnst. bedroom.
|
Final | 1/23/2015 | 1/23/2015 | 1/23/2015 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk left message 422.11 A) Overcurrent protection shall not exceed marking on appliance 422.31 Disconnecting means shall be provided for all permanently installed appliances
|
Rough-In Permanent Service | 11/13/2014 | 11/17/2014 | 11/17/2014 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|