Final | 4/1/2015 | 4/1/2015 | 4/1/2015 | P | PASS |
Daryl DeGrange
|
|
|
The access code is 1130 Phone #: ###-#### Inspection requested via web by Stephen Kren correction done, final ok
|
Final | 3/30/2015 | 3/31/2015 | 3/31/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Hall Bathroom 210.52(D) More than one basin, a receptacle is reqired adjacent to each basin location or one receptacle between the two basins. Stairway luminaires not working.
|
Final | 3/27/2015 | 3/30/2015 | 3/30/2015 | A | CANC |
Daryl DeGrange
|
|
|
Any questions please call, thx. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
|
Final | 3/24/2015 | 3/25/2015 | 3/25/2015 | A | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Kren Job not ready for final at this time
|
Rough-In Permanent Service | 12/18/2014 | 12/19/2014 | 12/19/2014 | A | PASS |
Cevyn Recla
|
|
|
The corrections have been made, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren corrections made, RI OK, PS, UG, N, OK
|
Rough-In Permanent Service | 12/17/2014 | 12/17/2014 | 12/17/2014 | P | FAIL |
Cevyn Recla
|
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren 310.15B 4/0 AL SER, 60*, max amp rating is 150 300.4 bored holes, nm shall be protected through bored holes with less than 1 1/4 inch to framing member edge 210.70.3 lighting outlets required, attic space with equipment requiring servicing 334.30 nm cable shall be supported at intervals not exceeding 4 1/2 foot 320.23 NM shall be protected withing 6 feet of attic access spoke to Terry
|
Rough-In Permanent Service | 12/16/2014 | 12/17/2014 | 12/17/2014 | A | CANC |
Cevyn Recla
|
|
|
Any questions please let me know, thx, TW. Phone #: ###-#### >> Inspection requested via web by Stephen Kren Inspection cancelled from web by: Stephen Kren
|