DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. No response from posted notices and or phone messages. This permit is EXPIRED. A new permit is required to complete this job.
|
Permanent Service | 12/1/2014 | 12/1/2014 | 12/1/2014 | P | PASS |
Cevyn Recla
|
|
|
Aaron// ###-####- Per Daryl Degrange PS, UG, RC, OK
|
Final | 11/25/2014 | 11/25/2014 | 11/25/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Breanne-please call for access Phone #: ###-#### 110.3- Terminations at old hot tub disconnect not compliant. -30amp breaker on 14 ga. wire.. -NM cable ran in damp or wet location in flex. -Grounded conductor strands split ti seperate terminations. -Multiple conductors terminated under single lugs listed for single conductors.
|
Permanent Service | 11/25/2014 | 11/25/2014 | 11/25/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Breanne-please call for access Phone #: ###-#### 250.52- Unable to verify grounding electrode system. 2 ground rods required for reconnect.
|