Final | 5/8/2015 | 5/11/2015 | 5/11/2015 | A | PASS |
Daryl DeGrange
|
|
|
Home owner will be home for access. Call Eric with any issues. Phone #: ###-#### Inspection requested via web by Eric Schroeder final ok
|
Electrical Rough-In | 2/25/2015 | 2/25/2015 | 2/25/2015 | P | PASS |
Cevyn Recla
|
|
|
Eric Phone #: ###-#### corrections made, RI OK
|
Electrical Rough-In | 2/23/2015 | 2/24/2015 | 2/24/2015 | A | FAIL |
Bob Reichert
|
|
|
key is under the mat at the back door Phone #: ###-#### Inspection requested via web by Eric Schroeder called, ledft correction notice, NEC 210.52(A)(1) shall install receptacle in new wall south side east bedroom,334.30 shall support and secure nm cable within 12" of panel, (rear of panel), 250.148 shall provide ground continuity in box (east wall, kitchen area)
|
Permanent Service | 11/26/2014 | 12/3/2014 | 12/3/2014 | P | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Eric Schroeder PS, OH, N, OK
|