Permanent Service | 12/8/2014 | 12/9/2014 | 12/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Please Call Gerald @###-#### To Gain Access To The Residence. We made All The Corrections And its ready To Energize Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett p/s u/g rec ok
|
Final | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | PASS |
Rock A. Hudson
|
|
|
Please Call Gerald @###-#### To Gain Access To The Residence. We made All The Corrections And its ready To Energize Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Service reconnect Final ok
|
Permanent Service | 12/3/2014 | 12/3/2014 | 12/3/2014 | P | FAIL |
Rock A. Hudson
|
|
|
This Is A Request For Permanent Service The House has been vacant for Over A Year. We Did A Walkthrough Yesterday And there Are Some issues For Sure. Please call Gerald With a 30 Minute Advance Notice To Get The House Opened Please Call Gerald @###-#### Thanks And Have the Best Day Ever! Phone #: ###-#### Inspection requested via web by jason shifflett 200.2- Grounding conductor unsed as grounded conductor at sub panel in closet off kitchen shall be insulated. 210.63- A lighting outlet and service receptical is required for heating equiptment located in crawl space. 250.53(D)(2)- Where metal water pipe is used as a grounding electrode system it shall be supplemented by additional rods. 300.3- Hot tub circuit shall be ran in a conduit or cable assembly. Remove or replace.
|