Permit Information
Permit NumberELE14-03350
StatusFinaled
Name SMITH WANDA G
Site Address 1309 W HOWARD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
wiring in a garage
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/29/20151/30/20151/30/2015APASS
DetailsRex Boyles
Ron Phone #: ###-#### final ok
Electrical Rough-In1/30/20151/30/20151/30/2015PPASS
DetailsRex Boyles
Ron Phone #: ###-#### corrections made r/i ok
Electrical Rough-In1/28/20151/29/20151/29/2015AFAIL
DetailsRock A. Hudson
Ron Phone #: ###-#### 314.16- Boxes shall have sufficient size to provide free air space for enclosed conductors.
300.4- Bored holes that do not maintain 1 1/4" shall have nail plates.
* Receptacle outlets located in garage shall be above 18" minimum.
Electrical Rough-In1/20/20151/20/20151/20/2015PCANC
DetailsCevyn Recla
Ron Phone #: ###-####
wrong inspection, see conference
Conference1/20/20151/20/20151/20/2015PDONE
DetailsCevyn Recla
Ron Phone #: ###-####
Discussion of requirements for adding receptacles in garage. GFI protection requirements, nail plates, etc.