Final | 12/24/2015 | 12/28/2015 | 12/28/2015 | A | PASS |
Bob Reichert
|
|
|
Jason Phone #: ###-#### ok final
|
Electrical Rough-In | 7/7/2015 | 7/8/2015 | 7/8/2015 | A | PASS |
Rock A. Hudson
|
|
|
JD Phone #: ###-#### Corrections done rough in ok cover
|
Electrical Rough-In | 7/6/2015 | 7/6/2015 | 7/6/2015 | P | FAIL |
Daryl DeGrange
|
|
|
would like call ahead; J.D. Phone #: ###-#### NEC 300.4 shall not staple NM cable within 1 1/4 of edge of framing member, NEC 334.30 Secure MN cable within 12in. of cabnet, device box. Grounded conductor in neutral bar and grounding conductors in ground bar, Decaded bathroom circuit not serve other receptacles of other rooms
|
Conference | 1/15/2015 | 1/15/2015 | 1/15/2015 | P | DONE |
Rex Boyles
|
|
|
JD Phone #: ###-#### discuss conversion of garage to liv. rm and bathroom. Discuss branch circuits, receptacles and switches and sm. detector wiring.
|