Final | 1/12/2015 | 1/13/2015 | 1/13/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt corrections made, Final OK
|
Final | 1/12/2015 | 1/12/2015 | 1/12/2015 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt called John 408.36D Backfed devices shall be secured in place by fastener 110.3 installation and use, equipment shall be installed according to instructions. Ground clamp is loose on ground rod.
|
Final | 1/8/2015 | 1/9/2015 | 1/9/2015 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 250.32 seperate building supplied by feeder or branch circuit shall have a grounding electrode system installed 250.32.D Seperate building or structure, disconnecting means required at nearest point of entrace called John
|
Rough-In Permanent Service | 1/7/2015 | 1/7/2015 | 1/7/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt service inspection only, PS, OH, N, OK
|