Final | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson final OK
|
Electrical Rough-In | 1/28/2015 | 1/29/2015 | 1/29/2015 | A | PASS |
Cevyn Recla
|
|
|
Inspect on Grid for Ceiling Phone #: ###-#### Inspection requested via web by David Nelson RI Ceiling cover ok
|
Electrical Rough-In | 1/15/2015 | 1/16/2015 | 1/16/2015 | A | FAIL |
Cevyn Recla
|
|
|
Ceiling cover inspection, call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson 300.11 independant means of secure support shall be provided, they shall be distinguishable by color ,tagging, or other means 300.11 cabling shall be supported by grid 358.30 emt shall be securely fastened within 3 ft. of boxes and conduit bodies 348.30 Flex shall be securely fastened within 12 inches of boxes and coduit bodies, and at intervals not exceeding 4 1/2 feet 110.12 unused openings shall be closed BCC 4.5.32 known code violations not to be retained
|
Rough-In Permanent Service | 1/7/2015 | 1/8/2015 | 1/7/2015 | A | DONE |
Cevyn Recla
|
|
|
inspection on walls only, adjacent unit Phone #: ###-#### Inspection requested via web by David Nelson Rough in Walls ok, see pmt. 15-00034
|