Final | 4/16/2015 | 4/16/2015 | 4/16/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton final ok
|
Final | 4/14/2015 | 4/15/2015 | 4/15/2015 | A | FAIL |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.24(A)- Available fault current shall be permenently labeled on main disconnect with date. 210.8(B)(2)-all 15 and 20amp 120volt receptacles shall be GFCI protected in non dwelling kitchens. Panel covers need to be in place with directories.
|
Electrical Rough-In | 4/9/2015 | 4/9/2015 | 4/9/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton t bar ceilings ok to cover
|
Electrical Rough-In | 3/19/2015 | 3/19/2015 | 3/19/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton light pole bases and signs pole bases and u.ground conduits r/i ok
|
Electrical Rough-In | 3/16/2015 | 3/16/2015 | 3/16/2015 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton at contractors request
|
Electrical Rough-In | 3/2/2015 | 3/3/2015 | 3/3/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i walls and soffits ok (except electrical room area not ready)
|
Electrical Rough-In | 2/17/2015 | 2/18/2015 | 2/18/2015 | A | PASS |
Rex Boyles
|
|
|
Cover inspection for Parapet walls only. Marcello will be on site ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok roof parapet walls
|
Electrical Rough-In | 2/9/2015 | 2/11/2015 | 2/9/2015 | P | CANC |
Rex Boyles
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton site u.ground r/i ok
|
Electrical Rough-In | 1/23/2015 | 1/23/2015 | 1/23/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i under slab conduits ok to cover
|
Electrical Rough-In | 1/13/2015 | 1/14/2015 | 1/14/2015 | A | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton grounding electrode ok
|
Electrical Rough-In | 1/12/2015 | 1/13/2015 | 1/13/2015 | P | NR |
Rex Boyles
|
|
|
Grounding Phone #: ###-#### Inspection requested via web by Kerri Hamilton not ready
|