Permit Information
Permit NumberELE15-00158
StatusFinaled
Name STEPHENS ELECTRIC INC
Site Address 3017 N BOGUS BASIN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/5/20153/5/20153/5/2015PPASS
DetailsRock A. Hudson
The corrections have been repaired as per the most recent inspection, any questions please let me know, thx! TW.
ACCESS CODE - 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren Final ok
Final2/26/20152/26/20152/26/2015PFAIL
DetailsCevyn Recla
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW.
the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren

Talked to worker on site
300.4 A NM through bored hole shall be protected when edge of hole is less than 1 1/4 inch from framing member edge
300.4 D NM shall be secured so outer edge of cable is not less than 1 1/4 inch from framing member edge
334.30 NM shall be secured within 12 inches of box.
Permanent Service2/26/20152/26/20152/26/2015PPASS
DetailsCevyn Recla
All the corrections have been completed and is ready for a final insp, any questions please let me know, thx, TW.
the ACCESS CODE is 4077 Phone #: ###-#### Inspection requested
via web by Stephen Kren

P/S, O/H, R/C, OK
Permanent Service1/21/20151/22/20151/22/2015ACANC
DetailsCevyn Recla
There hasn''t been a meter at this location for over a year, Idaho Power is requiring an inspection of the service before powering.
The ACCESS CODE is 4077 Phone #: ###-#### Inspection requested via web by Stephen Kren
250.53 Grounding electrode system required with supplemental grounding electrode
334.30 NM shall be secured within 12 inches of boxes
250.64 grounding electrodes shal be continyuous or a permitted splicing method used
200.7 ungrounded conductors shall be permanently re-identified
250.104 metal piping shall be bonded to service enclosure
300.4 cables through bored holes shall be protected
210.4 multi wire branch circuits shall have handle ties, or you can remove splices in neutrals and land them to the bar
open boxes shall be closed, disconnected cables shall be properly terminated or removed
bundling of cables not allowed
210.8.5 GFI protection required unfinished basement
cables and boxes are hanging directly from ceiling, need repaired
BCC 4.5.32 Known code violations not to be retained