Permit Information
Permit NumberELE15-00199
StatusFinaled
Name ECO ELECTRIC
Site Address 11301 W GOLDENROD AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Complete rewire after fire
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/29/20156/30/20156/30/2015APASS
DetailsRock A. Hudson
code #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
Final6/29/20156/29/20156/29/2015PFAIL
DetailsRock A. Hudson
Code #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder 210.8- All receptacle outlets serving counter top shall have GFCI protection. to right of sink
Electrical Rough-In3/23/20153/23/20153/23/2015PPASS
DetailsRock A. Hudson
code #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder Rough in ok cover
Electrical Rough-In3/20/20153/20/20153/20/2015PFAIL
DetailsRock A. Hudson
lock box #0363 Phone #: ###-#### Inspection requested via web by Eric Schroeder 210.52(I)- Foyer walls 3' or longer shall have receptacle outlet installed.
Minimum of 13 rooms need to be added to permit.
Check branch circuit termination in panel, not complete at rough in
Permanent Service1/26/20151/27/20151/27/2015APASS
DetailsRock A. Hudson
Please call Eric 30 mins before. Phone #: ###-#### Inspection requested via web by Eric Schroeder All existing circuits have been cut so they cannot be reused. Reconnect for temp power located below panel. p/s u/g rec ok