Permit NumberELE15-00256
StatusFinaled
Name MCLAIN ELECTRIC LLC
Site Address 6932 W STATE ST
Project NameYogurt Court #3
Customer Number 15-00201
ePlanReviewNo
Description
Electrical Permit - Alteration: RE-WIRE FOR NEW STORE EQUIPMENT
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/30/20153/31/20153/31/2015PPASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Gerald McLain correction done, final ok
Electrical Rough-In3/30/20153/31/20153/31/2015PPASS
DetailsDaryl DeGrange
ceiling rough re-inspection Phone #: ###-#### Inspection requested via web by Gerald McLain rough-in ok cover ceiling grid
Electrical Rough-In3/29/20153/30/20153/30/2015PFAIL
DetailsBob Reichert
CEILING ROUGH ELECTRICAL INSPECTION Phone #: ###-#### Inspection requested via web by Gerald McLain left correction notice, told wireman to be sure and have license on person, NEC 725.25 shall remove abandoned lv cables,300.11 grid shall not support cables and raceways
Electrical Rough-In3/12/20153/12/20153/12/2015APASS
DetailsDaryl DeGrange
correction done,Rough-in ok cover walls
Electrical Rough-In3/10/20153/11/20153/11/2015PFAIL
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Gerald McLain NEC 330.30(A) Securing MC cable witin 12 in. od cable termination, NEC 362.12(9) Uses not permited, Where subject to physical damage.