Final | 4/13/2015 | 4/13/2015 | 4/13/2015 | P | PASS |
Daryl DeGrange
|
|
|
Homeowners are out of town. Please call Emmet 1 hour before inspection so I can meet for access ###-#### Phone #: ###-#### Inspection requested via web by Emmet Bushman final ok
|
Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 | P | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman check for multi wire handle tie at final, RI ok to cover
|
Electrical Rough-In | 2/5/2015 | 2/6/2015 | 2/6/2015 | A | FAIL |
Cevyn Recla
|
|
|
New kitchen wiring Phone #: ###-#### Inspection requested via web by Emmet Bushman called contractor 300.13 (B) Device Removal. In multiwire branch circuits, the continuity of a grounded conductor shall not depend on device connections such as lampholders, receptacles, and so forth, where the removal of such devices would interrupt the continuity 300.4 1 nm through bored holes shall have protection where edge of hole is less than 1 1/4 inch from edge of framing member 300.4 2 where cable is run through notches in wood, it shall be protected by steel plate 210.4 B multi wire branch circuits shall have means to disconnect all ungrounded conductors simultaneously
|