Permit Information
Permit NumberELE15-00316
StatusFinaled
Name TRADITIONAL ELECTRIC
Site Address 5505 N CRIMSON WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: Wiring for new kitchen
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/13/20154/13/20154/13/2015PPASS
DetailsDaryl DeGrange
Homeowners are out of town. Please call Emmet 1 hour before inspection so I can meet for access ###-#### Phone #: ###-#### Inspection requested via web by Emmet Bushman final ok
Electrical Rough-In2/6/20152/6/20152/6/2015PPASS
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by Emmet Bushman
check for multi wire handle tie at final, RI ok to cover
Electrical Rough-In2/5/20152/6/20152/6/2015AFAIL
DetailsCevyn Recla
New kitchen wiring Phone #: ###-#### Inspection requested via web by Emmet Bushman called contractor
300.13 (B) Device Removal. In multiwire branch circuits, the
continuity of a grounded conductor shall not depend on
device connections such as lampholders, receptacles, and
so forth, where the removal of such devices would interrupt
the continuity
300.4 1 nm through bored holes shall have protection where edge of hole is less than 1 1/4 inch from edge of framing member
300.4 2 where cable is run through notches in wood, it shall be protected by steel plate
210.4 B multi wire branch circuits shall have means to disconnect all ungrounded conductors simultaneously