Final | 5/19/2015 | 5/19/2015 | 5/19/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI final ok
|
Final | 5/18/2015 | 5/18/2015 | 5/18/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Switched power on back patio lighting, label main breaker, provide at least 50% CFL`s to meet 2012 energy code requirements
|
Rough-In Permanent Service | 2/11/2015 | 2/12/2015 | 2/12/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI corrections made, RI OK, P/S, U/G, N, OK
|
Rough-In Permanent Service | 2/9/2015 | 2/10/2015 | 2/10/2015 | A | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 300.4 (1) Bored Holes. In both exposed and concealed locations, where a cable- or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 32 mm (11/4 in.) from the nearest edge of the wood member. Where this distance cannot be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate(s) or bushing(s), at least 1.6 mm (1/16 in.) thick, and of appropriate length and width installed to cover the area of the wiring. 210.52 B 2 The two or more small appliance branch circuits shall supply no other outlets 210.52 I Foyers 60 square feet or larger shall have receptacles on walls 3 foot or larger 210.8 GFI must be readily accessible called TOM
|