Final | 3/11/2015 | 3/12/2015 | 3/12/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Thaniel Bishop With documentation provided clarifing grounding requirements and UL listings for system installed. 690.35 requirements for ungrounded systems have been satified. Final ok
|
Final | 2/16/2015 | 2/18/2015 | 2/19/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Thaniel Bishop 210.8(A)(2) All 15 and 20 ampere 120 volt garage receptacles require GFCI protection. Photovoltaic monitoring equipment. NEC 690.35 (F) Warning Label Article 690.35 Ungrounded Photovoltaic Power Sytems under review, NEC 690.47 Grounding Electrode System
|