Final | 3/4/2015 | 3/4/2015 | 3/4/2015 | P | PASS |
Bob Reichert
|
|
|
Needing ceiling and final inspection. Please call Brad (###-####) for access. Phone #: ###-#### Inspection requested via web by Brad Girard ok cover ceiling, ok final, signed card
|
Electrical Rough-In | 2/12/2015 | 2/13/2015 | 2/13/2015 | A | PASS |
Cevyn Recla
|
|
|
Please call Jim (###-####) 30 minutes ahead for access, best parking is at the back of the building. Phone #: ###-#### Inspection requested via web by Brad Girard discused with contractor, he will fish in replacement wiring to existing rooms, 517.13 all cirucits serving patient care areas be provided with effective ground path, lane 1 and 2, exam room, contact fitting room 517.18 B patient areas shall be provided 8 receptacles. they shall be listed hospital grade. 300.11 cables shall not be supported by grid ceiling, wall cover ok
|