Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE15-00397
StatusFinaled
Name TRADITIONAL ELECTRIC
Site Address 1219 E WASHINGTON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/18/20155/18/20155/18/2015PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Emmet Bushman final ok
Final5/15/20155/18/20155/18/2015APASS
DetailsRex Boyles
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman corrections made final ok
Final5/12/20155/13/20155/13/2015AFAIL
DetailsRock A. Hudson
Key in back weather proof outlet for house
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman 230.79- For service on detached garage with more than 2 circuits disconnecting means shall be rated 60 amp minimum.
250.24(A)(5)- Grounded conductor shall not be connected to noncurrent carrying metal parts on load side of main disconnect,
408.36(D)- Plug in type back fed breakers shall be secured by additional means.
422.30- Range hood and house fan shall have disconnecting means.
Rough-In Permanent Service2/16/20152/17/20152/17/2015APASS
DetailsDaryl DeGrange
re-inspect house for nail plates, trench depth between house and garage Phone #: ###-#### Inspection requested via web by Emmet Bushman rough-in house and detacted garage p/s u/g n ok
Rough-In Permanent Service2/12/20152/13/20152/13/2015PFAIL
DetailsCevyn Recla
Phone #: ###-#### Inspection requested via web by Emmet Bushman
no access to upstairs of garage area.
300.4 Nail plates, framing members with less than 1 1/4 inch clearance to framing member edge require protection
called Emmett