Final | 5/18/2015 | 5/18/2015 | 5/18/2015 | P | PASS |
Rex Boyles
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman final ok
|
Final | 5/15/2015 | 5/18/2015 | 5/18/2015 | A | PASS |
Rex Boyles
|
|
|
Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman corrections made final ok
|
Final | 5/12/2015 | 5/13/2015 | 5/13/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Key in back weather proof outlet for house Garage code 0713 Phone #: ###-#### Inspection requested via web by Emmet Bushman 230.79- For service on detached garage with more than 2 circuits disconnecting means shall be rated 60 amp minimum. 250.24(A)(5)- Grounded conductor shall not be connected to noncurrent carrying metal parts on load side of main disconnect, 408.36(D)- Plug in type back fed breakers shall be secured by additional means. 422.30- Range hood and house fan shall have disconnecting means.
|
Rough-In Permanent Service | 2/16/2015 | 2/17/2015 | 2/17/2015 | A | PASS |
Daryl DeGrange
|
|
|
re-inspect house for nail plates, trench depth between house and garage Phone #: ###-#### Inspection requested via web by Emmet Bushman rough-in house and detacted garage p/s u/g n ok
|
Rough-In Permanent Service | 2/12/2015 | 2/13/2015 | 2/13/2015 | P | FAIL |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman no access to upstairs of garage area. 300.4 Nail plates, framing members with less than 1 1/4 inch clearance to framing member edge require protection called Emmett
|