Final | 2/18/2015 | 2/18/2015 | 2/18/2015 | P | PASS |
Rock A. Hudson
|
|
|
Ron Phone #: ###-#### Corrections done Final ok
|
Final | 2/17/2015 | 2/17/2015 | 2/17/2015 | P | FAIL |
Cevyn Recla
|
|
|
call for more info and so someone can meet you. Phone #: ###-#### Inspection requested via web by ron spen cer Old work that was never permitted or inspected, the contractor will open a few boxes for inspection of make up when we come back for the corrections. 408.4 Every circuit to be legibly identified for its purpose 110.4.A.7 Mechanical strength of parts_ outlet will not hold cord 210.4.B Multi wire branch circuit shall be supplied by means to disconnect all ungrounded conductors simultaneously 250.119 Grounding conductors shall be bare, green, or green with yellow stripe, ungrounded circuit in panel with green wire needs changed.
|