Permit Information
Permit NumberELE15-00442
StatusExpired
Name BAR XL
Site Address 2900 N WOODY DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - Alteration: power off over one year inspection
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired2/4/20192/4/20192/4/2019PPASS
DetailsDaryl DeGrange
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
Permanent Service5/21/20155/21/20155/21/2015APASS
DetailsBob Reichert
Will label panel when power is back on. Phone #: ###-#### Inspection requested via web by Jason Wicks p/s o/h rec ok
Final2/20/20152/20/20152/20/2015PCANC
DetailsCevyn Recla
needed PS inspection
Permanent Service2/20/20152/20/20152/20/2015PPASS
DetailsCevyn Recla
P/S, O/H, R/C, OK
Final2/19/20152/19/20152/19/2015PFAIL
DetailsCevyn Recla
I am trying to get an energize service for this house. I did not see it in the drop down menu so I checked final Phone #: ###-#### Inspection requested via web by Jason Wicks
250.24 Grounding electrode system required
408.41 each grounded conductror shall terminate in an individual terminal that is als not used for another conductor
210.4 B Multi wire branch circuits shall be supplied with a means to disconnect all ungrounded conductors simultaneously
408.36 D Backfed devices shall be secured in place by additional means
250.104 Metal water piping shall be bonded
110.26 Working space for electrical equipment to be maintained, 3 foot clearance required
334.15 Romex shall be protected from physical damage
BCC. 4-05-32 Known code violations not to be retained. When altering a pre-existing electrical wire, equipment, apparatus or fixture, or adding any new
wiring, the existing electrical wiring in close proximity shall be in accordance with the present
code
250.24.5 Load side gronding connections, grounded conductor shall not be connected to non current carrying metal parts, seperated neutral and ground at subpanel
IDPCO contacted to place lock on meter, as seal has been removed