Final | 3/20/2015 | 3/23/2015 | 3/23/2015 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn final ok
|
Rough-In Permanent Service | 2/23/2015 | 2/24/2015 | 2/24/2015 | A | PASS |
Cevyn Recla
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn corrections made, RI OK P/S, U/G, N, OK
|
Rough-In Permanent Service | 2/20/2015 | 2/23/2015 | 2/23/2015 | A | FAIL |
Cevyn Recla
|
|
|
Thanks Phone #: ###-#### Inspection requested via web by Darryn Coburn called 300.4 NM cable through bored holes shall have protection where edge of bored hole is less than 1 1/4 inch from edge of framing member 320.23 Guard stripps required within six foot of attic access 300.13 B Multi wire branch circuit grounded conductor can not depend on device 406.5 Srews used for attaching receptacles to a box shall be a machine type screw having 32 threads per inch
|