Final | 3/3/2015 | 3/5/2015 | 3/5/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
Permanent Service | 2/24/2015 | 2/25/2015 | 2/25/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Inside panel changed out. Metering remained the same. Any questions, please call Steve at ###-####. Thanks Phone #: ###-#### Inspection requested via web by Barbara Szurgot 250.53(D)(2)- If used as grounding electrode, underground water pipe shall be supplemented by an additional grounding electrode. 250.92(B)- (B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s).
|