Final | 3/5/2015 | 3/6/2015 | 3/6/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan correction made, ok final
|
Final | 3/4/2015 | 3/5/2015 | 3/5/2015 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan called, told contractor that no access, NEC 110.26 requires 30" width and 36" depth for 0-150 volts, could possibly rotate equipment
|