DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Final | 3/18/2015 | 3/18/2015 | 3/18/2015 | P | CANC |
Rock A. Hudson
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Needed permanent service
|
Permanent Service | 3/18/2015 | 3/18/2015 | 3/18/2015 | P | PASS |
Rock A. Hudson
|
|
|
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Remodel to include new kitchen cabinet layout outlets to be added to serve counter top and laundry changing to bath. p/s o/h rec ok
|
Permanent Service | 3/11/2015 | 3/12/2015 | 3/12/2015 | A | FAIL |
Rex Boyles
|
|
|
Inspection for power off more than one year, call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson Nec 250.26-overhead service conductors need to be 10 minimum to finish grade, 230.28-overhead service conductors thru roof need to be of adequate strength. 250.104 and 250.52-metal underground pipe shall be bonded to service and in the first 5 foot of entering bldg. 250.52(5) and 250.53(A)(3) and 250.53(B)(2) 2 ground rods required (supplemental grounding electrode). 250.94 intersystem ground terminal strip required. Need insulated nuetral to sub panel. Range and dryer need to be 4 wire system. Boise municipal code 4-05-32
|