Final | 3/17/2016 | 3/18/2016 | 3/18/2016 | A | PASS |
Rex Boyles
|
|
|
JR (husband) Phone #: ###-#### corrections made final ok
|
Final | 3/10/2016 | 3/11/2016 | 3/11/2016 | A | NR |
Bob Reichert
|
|
|
JR Phone #: ###-#### called, told to strap conduit, ground wire, label breakers, recall
|
Permanent Service | 2/16/2016 | 2/19/2016 | 2/19/2016 | A | PASS |
Rex Boyles
|
|
|
JR Phone #: ###-#### p/s o/h rec ok
|
ELE-Request for Extension | 2/17/2016 | 2/19/2016 | 2/19/2016 | A | PASS |
Rex Boyles
|
|
|
JR// please call before Phone #: ###-#### extension ok
|
Permanent Service | 6/30/2015 | 7/2/2015 | 7/2/2015 | A | NR |
Rex Boyles
|
|
|
JR-call prior to meet Phone #: ###-#### will call again for p/s when service is moved to shop wall
|
Permanent Service | 5/4/2015 | 5/5/2015 | 5/5/2015 | A | PASS |
Rex Boyles
|
|
|
JR Phone #: ###-#### p/s o/h n ok Note: temp. location. Will be moved to new bldg. wall after being built.
|
Temporary Service | 4/27/2015 | 4/30/2015 | 4/30/2015 | P | FAIL |
Rex Boyles
|
|
|
JR - husband Phone #: ###-#### #4 alum ground wire required with feeders to house. Entrance hub required in top of service panel for riser. Plastic bushings required with #4 conductors or larger. Ground rods need to be minimum of 6 foot apart. Add 2nd ground rod at house. Separate ground wires and nuetral wires at house panel. Call in for perm. service when ready.
|