Final | 12/15/2015 | 12/15/2015 | 12/15/2015 | P | PASS |
Eric Story
|
|
|
Call James if any issues. Corrections have been made.
Thanks Phone #: ###-#### Inspection requested via web by John Harvey homeowner said the hot tub will not be be set where it is at this point. corrections fixed final ok
|
Final | 12/13/2015 | 12/14/2015 | 12/14/2015 | A | FAIL |
Eric Story
|
|
|
Garage code is 1201. James will be available by phone. Tim will also be in and out of the residence all day long. His number is ###-####.
Phone #: ###-#### Inspection requested via web by John Harvey 210.8 (3) all outdoor receptacles shall have GFCI protrection-210.8 (7) all receptacles located wihin 6' of a sink shall have GFCI protection-210.8 (5) all 120v receptacles in a unfinished basement shall have GFCI protection-422.31 all permanently installed appliances shall have a means of lockout(dishwasher and hood) 406.12 all receptacles shall be tamper resistant(a few down stairs)-314.20 recessed boxes in tile shall have a listed extender-250.94 intersystem bond required-680.22 no receptacles shall be located within 6' of a hot tub
|
Rough-In Permanent Service | 11/11/2015 | 11/12/2015 | 11/12/2015 | P | PASS |
Daryl DeGrange
|
|
|
Conduit is replaced Phone #: ###-#### Inspection requested via web by John Harvey p/s u/g n ok
|
Permanent Service | 11/10/2015 | 11/10/2015 | 11/10/2015 | A | FAIL |
Daryl DeGrange
|
|
|
Riser is installed panel. John will be on tomorrow
Call Tim if any problems
Thanks
Tim Phone #: ###-#### Inspection requested via web by John Harvey NEC 352.12 Exposed PVC where subject to physical damage shall be schedule 80. NEC 352.30 Securing, siding is in place. NEC 352.44 Expansion fitting is required
|
Electrical Rough-In | 11/2/2015 | 11/2/2015 | 11/2/2015 | P | PASS |
Rex Boyles
|
|
|
House will be open. And James will be on site doing electrical trim.
Master bathroom floor heat rough in inspection only.
Thanks
Phone #: ###-#### Inspection requested via web by John Harvey r/i ok floor heat
|
Electrical Rough-In | 6/11/2015 | 6/11/2015 | 6/11/2015 | P | PASS |
Eric Story
|
|
|
Jeff is on site. Thank you. Tim Phone #: ###-#### Inspection requested via web by John Harvey service outlet required rough-in ok
|