Permit Information
Permit NumberELE15-01056
StatusFinaled
Name GOLDEN ELECTRIC
Site Address 1201 E FRANKLIN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical Permit - New: New construction of a 2950 square foot single family dwelling.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/15/201512/15/201512/15/2015PPASS
DetailsEric Story
Call James if any issues. Corrections have been made.

Thanks
Phone #: ###-#### Inspection requested via web by John Harvey homeowner said the hot tub will not be be set where it is at this point. corrections fixed final ok
Final12/13/201512/14/201512/14/2015AFAIL
DetailsEric Story
Garage code is 1201. James will be available by phone. Tim will also be in and out of the residence all day long. His number is ###-####.

Phone #: ###-#### Inspection requested via web by John Harvey 210.8 (3) all outdoor receptacles shall have GFCI protrection-210.8 (7) all receptacles located wihin 6' of a sink shall have GFCI protection-210.8 (5) all 120v receptacles in a unfinished basement shall have GFCI protection-422.31 all permanently installed appliances shall have a means of lockout(dishwasher and hood) 406.12 all receptacles shall be tamper resistant(a few down stairs)-314.20 recessed boxes in tile shall have a listed extender-250.94 intersystem bond required-680.22 no receptacles shall be located within 6' of a hot tub
Rough-In Permanent Service11/11/201511/12/201511/12/2015PPASS
DetailsDaryl DeGrange
Conduit is replaced Phone #: ###-#### Inspection requested via web by John Harvey p/s u/g n ok
Permanent Service11/10/201511/10/201511/10/2015AFAIL
DetailsDaryl DeGrange
Riser is installed panel. John will be on tomorrow

Call Tim if any problems

Thanks

Tim Phone #: ###-#### Inspection requested via web by John Harvey NEC 352.12 Exposed PVC where subject to physical damage shall be schedule 80. NEC 352.30 Securing, siding is in place. NEC 352.44 Expansion fitting is required
Electrical Rough-In11/2/201511/2/201511/2/2015PPASS
DetailsRex Boyles
House will be open. And James will be on site doing electrical trim.

Master bathroom floor heat rough in inspection only.

Thanks

Phone #: ###-#### Inspection requested via web by John Harvey r/i ok floor heat
Electrical Rough-In6/11/20156/11/20156/11/2015PPASS
DetailsEric Story
Jeff is on site. Thank you. Tim Phone #: ###-#### Inspection requested via web by John Harvey service outlet required rough-in ok