Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | PASS |
Rex Boyles
|
|
|
building shall be unlocked. thanks Phone #: ###-#### Inspection requested via web by Paula Gratiot corrections made final ok
|
Final | 5/28/2015 | 5/29/2015 | 5/29/2015 | A | FAIL |
Rex Boyles
|
|
|
Luke is Orbit Pizza sight foreman. His number is ###-####. He has been advised to have the building unlocked. (Jim is out of town on 5-29 and out of cell phone range) Dustin is in our office at ###-####. Thanks. Inspection requested via web by Paula Gratiot Temporary occupancy OK. Rooftop abondoned conduit and wiring to be removed when roof work is done prior to opening of store. Rooftop receptacle shall be GFCI protected with in use cover. 210.8(B)(2)- all 120volt receptacles in non dwelling kitchens shall be GFCI protected. (behind reach in coolers) KO seal needed in j box on top of walk in cooler. ARC flash sticker needed on all loadcenters.
|
Final | 5/26/2015 | 5/27/2015 | 5/27/2015 | P | NR |
Rex Boyles
|
|
|
Luke is the foreman at Orbit Pizza. His number is ###-####. He should have it unlocked for you. Phone #: ###-#### Inspection requested via web by Paula Gratiot not ready
|
Electrical Rough-In | 4/20/2015 | 4/21/2015 | 4/21/2015 | A | PASS |
Rex Boyles
|
|
|
This is rough inspection of the walls please. On Site Foreman is Luke at ###-#### Phone #: ###-#### Inspection requested via web by Paula Gratiot r/i walls ok
|