Final | 8/18/2015 | 8/19/2015 | 8/19/2015 | A | PASS |
Bob Reichert
|
|
|
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok final, signed card
|
Final | 8/17/2015 | 8/18/2015 | 8/18/2015 | A | PART |
Bob Reichert
|
|
|
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton called, ok except shall install riser strap, intersystem grounding bar, then recall for final
|
Permanent Service | 8/10/2015 | 8/11/2015 | 8/11/2015 | A | PASS |
Bob Reichert
|
|
|
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton p/s u/g n ok
|
Permanent Service | 8/10/2015 | 8/10/2015 | 8/10/2015 | P | FAIL |
Bob Reichert
|
|
|
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton called, available fault current not posted
|
Electrical Rough-In | 7/21/2015 | 7/21/2015 | 7/21/2015 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton corrections made, ri ok
|
Electrical Rough-In | 7/20/2015 | 7/21/2015 | 7/21/2015 | A | FAIL |
Bob Reichert
|
|
|
First thing if possible please. Phone #: ###-#### Inspection requested via web by Kerri Hamilton called, left correction notice, NEC 300.4(A) edge of bored hole shall be 1 1/4" from edge of framing member, 330.30(B) shall secure mc cable within 12" of box
|
Electrical Rough-In | 7/20/2015 | 7/20/2015 | 7/20/2015 | P | NR |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton called, electrican still doing mud rings, make-up
|
Temporary Service | 6/24/2015 | 6/24/2015 | 6/24/2015 | P | CANC |
Bob Reichert
|
|
|
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton called, contractor shall purchase t/s permit
|
Electrical Rough-In | 6/12/2015 | 6/15/2015 | 6/15/2015 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton ok cover concrete encased electrode only
|