Final | 4/7/2016 | 4/8/2016 | 4/8/2016 | P | PASS |
Rock A. Hudson
|
|
|
Please contact Danny with any questions. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
|
Final | 4/6/2016 | 4/7/2016 | 4/7/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Contact is Danny Bridgewater Phone #: ###-#### Inspection requested via web by Stacie Tasker Pole receptacles not working, N. W. corner, centrally located along Gratz near entrance, In ground box broken, bushings on conduits. All mill woork on interior ok
|
Electrical Rough-In | 12/7/2015 | 12/8/2015 | 12/8/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need an underground inspection, please. Call Danny prior to arrival. Phone #: ###-#### Inspection requested via web by Stacie Tasker Underground to 15 central pole locations. Rough in ok cover
|
Final | 11/2/2015 | 11/3/2015 | 11/3/2015 | A | PART |
Rex Boyles
|
|
|
We need the final on the Car Wash. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker final ok on rooftop GFCIs, lube bays GFCIs ok, car wash final ok also. Showroom showindows receptacles ok EXCEPT rm 101(accessory vehicle) area not completed. Signed temp. occupancy card
|
Final | 10/29/2015 | 10/30/2015 | 10/30/2015 | P | PART |
Rock A. Hudson
|
|
|
Please contact Danny prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Check EPD for heat tape, WR recepts on roof, GFI 1/2 wall service, GFI for quick lube. OK occupy service area, detail area, RT bath off lounge, riser rm, compressor/oil room, quick lube.
|
Final | 10/28/2015 | 10/30/2015 | 10/29/2015 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
|
Final | 10/26/2015 | 10/28/2015 | 10/28/2015 | P | PART |
Rock A. Hudson
|
|
|
WE need a Final Temp occupancy, please. If you have any questions, please contact Danny at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Still need west showroom outlets, rt bath off lounge, roof, riser rm, compressor/oil storage room, quick lube, car wash, receptacle outlet with in 50' of service, parking lot recepts, additional parking area yet to finish. Offices and lounge areas ok occupy
|
Electrical Rough-In | 10/20/2015 | 10/21/2015 | 10/21/2015 | P | PASS |
Rock A. Hudson
|
|
|
WE need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker This will complete grid areas. Misc tiles will be left out where open boxes noticed. Showroom grid rough in ok cover
|
Electrical Rough-In | 10/19/2015 | 10/20/2015 | 10/20/2015 | P | PASS |
Rock A. Hudson
|
|
|
We need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Service receiving, service waiting, parts sales, accessory room grid rough in ok cover.
|
Electrical Rough-In | 10/16/2015 | 10/19/2015 | 10/19/2015 | A | CANC |
Rock A. Hudson
|
|
|
We need a ceiling inspection, please. Phone #: ###-#### Inspection requested via web by Stacie Tasker Contractor asked to cancel. will reschedule
|
Electrical Rough-In | 10/13/2015 | 10/14/2015 | 10/14/2015 | P | PASS |
Rock A. Hudson
|
|
|
We need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Business offices, tech. rm, copy/fax, F&I office, east hall, employee break rm and hall grid rough in ok cover
|
Permanent Service | 10/8/2015 | 10/9/2015 | 10/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker 100K rated main, current technologies has done performance test. p/s u/g n ok
|
Electrical Rough-In | 10/9/2015 | 10/9/2015 | 10/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker Only areas listed. New car receiving, sales offices, sales managers offices, east showroom boarders, general managers office, conference room, kitchen and lunch room, customer kitchen ceiling grid rough in ok cover
|
Electrical Rough-In | 10/5/2015 | 10/6/2015 | 10/6/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need a grid inspection for tomorrow. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Grid tiles near couple open boxes to remain open. Auto repair bay area grid rough in ok cover
|
Electrical Rough-In | 9/9/2015 | 9/14/2015 | 9/11/2015 | P | CANC |
Rock A. Hudson
|
|
|
We need a wall cover inspection for afternoon. Site contact is Mike Poff Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
|
Electrical Rough-In | 9/11/2015 | 9/11/2015 | 9/11/2015 | P | FAIL |
Rock A. Hudson
|
|
|
NEC 210.62- Show Windows. At least one 125-volt, singlephase, 15- or 20-ampere-rated receptacle outlet shall be installed within 450 mm (18 in.) of the top of a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width.
|
Electrical Rough-In | 9/9/2015 | 9/10/2015 | 9/10/2015 | P | PASS |
Rock A. Hudson
|
|
|
We need a wall cover inspection for afternoon. Site contact is Mike Poff Phone #: ###-#### Inspection requested via web by Stacie Tasker Discussed the absence of show window receptacle outlets, shall be required as per 210.63. Kitchen area, 1/2 walls, and offices as noted on contractor print wall rough in ok cover
|
Electrical Rough-In | 9/8/2015 | 9/9/2015 | 9/9/2015 | P | PASS |
Rock A. Hudson
|
|
|
Mike Poff is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Offices walls near kitchen as noted on contractor print rough in ok cover
|
Electrical Rough-In | 8/31/2015 | 9/2/2015 | 9/2/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Stacie Tasker Conference, lunch rm, kitchen, offices as noted on contractor print wall. rough in ok cover
|
Electrical Rough-In | 8/19/2015 | 8/20/2015 | 8/20/2015 | A | PASS |
Rock A. Hudson
|
|
|
Mike Poff is the site contact Phone #: ###-#### Inspection requested via web by Stacie Tasker Bathrooms wall and central hardlid rough in ok cover
|
Electrical Rough-In | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | PASS |
Eric Story
|
|
|
We need an underground inspection, please. Site contact is Mike Poff. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker street lights underground ok cover
|
Electrical Rough-In | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need an underground inspection for today, site contact is Mike Poff Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Electrical room underground rough in ok cover
|
Electrical Rough-In | 5/22/2015 | 5/26/2015 | 5/26/2015 | A | PASS |
Rock A. Hudson
|
|
|
Danny Phone #: ###-#### South half under ground rough in ok cover
|
Electrical Rough-In | 5/21/2015 | 5/22/2015 | 5/22/2015 | A | PART |
Rock A. Hudson
|
|
|
WE need an underground inspection for Friday, site contact is Mike Poff, he can be reached at ###-#### Phone #: ###-#### Inspection requested via web by Stacie Tasker underslab rough-in as noted on contractor print
|
Electrical Rough-In | 5/14/2015 | 5/15/2015 | 5/15/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need an underground inspection, site contact will be Mike Poff, he can be reached at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Homerun conduits to north underground rough in ok cover
|
Electrical Rough-In | 4/29/2015 | 4/30/2015 | 4/30/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need an underground inspection. Danny will be on site. Phone #: ###-#### Inspection requested via web by Stacie Tasker Feeders and sub-feed underground rough in ok cover
|
Electrical Rough-In | 4/23/2015 | 4/24/2015 | 4/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
We need an underground inspection. Please notify Danny 40 min prior to arrival so he can meet you there. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Underground feeders rough in ok cover
|