Final | 8/6/2015 | 8/6/2015 | 8/6/2015 | P | PASS |
Eric Story
|
|
|
Call for access code - Ron Phone #: ###-#### final ok
|
Final | 4/24/2015 | 4/24/2015 | 4/24/2015 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Needed rough permenant service inspection
|
Rough-In Permanent Service | 4/24/2015 | 4/24/2015 | 4/24/2015 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 4/23/2015 | 4/23/2015 | 4/23/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer Idaho Power requires an expansion joint in service riser. 300.4- NM cable shall be protected by nail plates when ran through holes less than 1 1/4" from framing surface or notched wood. 334.23- NM cable shall be protected from physical damage when ran in an accessible attic within 7' of attic access. 110.12(B)- Loose neutral in panel.
|