DOC - Permit Expired | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Conference | 7/31/2015 | 8/3/2015 | 8/3/2015 | A | DONE |
Rock A. Hudson
|
|
|
Call two hours before // Jason Phone #: ###-#### Discussed correction from previous inspection.
|
Electrical Rough-In | 8/3/2015 | 8/3/2015 | 8/3/2015 | P | PASS |
Rock A. Hudson
|
|
|
Call two hours before // Jason Phone #: ###-#### Rough in ok cover
|
Electrical Rough-In | 7/6/2015 | 7/7/2015 | 7/7/2015 | A | FAIL |
Rock A. Hudson
|
|
|
would like call ahead; Jason Phone #: ###-#### Owner did not call for a conference. 210.12(C)(3)-All 120 volt receptacle outlets located in bath area shall be on a dedicated 20 amp circuit and shall have no other outlets. 240.3(C)- 20 amp circuits shall be completed with 12 ga. wiring. 300.4- NM cable shall be secured at least 1 1/4" from framing surface. 314.16- Box fill shall not exceed rating on box. BCC- Roof shall have moisture barrier installed. NM cable not rated for exposure to weather. BCC- Make up shall be completed and boxes shall be installed at all light locations.
|