Final | 6/29/2015 | 6/30/2015 | 6/30/2015 | A | PASS |
Rex Boyles
|
|
|
Joel Phone #: ###-#### correction made final ok
|
Final | 6/26/2015 | 6/26/2015 | 6/26/2015 | P | PART |
Eric Story
|
|
|
Joel Phone #: ###-#### verify water deversion above panel in basement for final
|
Electrical Rough-In | 6/23/2015 | 6/24/2015 | 6/24/2015 | A | PASS |
Rex Boyles
|
|
|
Please provide us with a ceiling inspection. Joel Hudson Phone #: ###-#### Inspection requested via web by Kevin Perez r/i t bar ceilings ok to cover
|
Electrical Rough-In | 6/5/2015 | 6/8/2015 | 6/8/2015 | A | PASS |
Daryl DeGrange
|
|
|
Mike Phone #: ###-#### rough-in ok concrete encased feeders
|
Electrical Rough-In | 6/3/2015 | 6/4/2015 | 6/4/2015 | A | PASS |
Daryl DeGrange
|
|
|
Joel Phone #: ###-#### rough-in ok cover walls
|
Electrical Rough-In | 6/1/2015 | 6/1/2015 | 6/2/2015 | P | PASS |
Daryl DeGrange
|
|
|
rough-in ok cover basement ceiling
|
Conference | 5/29/2015 | 6/1/2015 | 6/1/2015 | P | DONE |
Daryl DeGrange
|
|
|
Joel Phone #: ###-#### Discussed unfused service conductors entering building structure requiring minimun 2 inch concrete encasement.
|
Electrical Rough-In | 5/29/2015 | 5/29/2015 | 5/29/2015 | P | NR |
Bob Reichert
|
|
|
Joel Phone #: ###-#### no electrician on site, called several times, phone not working, left correction notice, BCC not ready, no violations shall be retained- service, left do not cover card
|