Final | 8/14/2015 | 8/14/2015 | 8/14/2015 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams final ok
|
Final | 7/31/2015 | 7/31/2015 | 7/31/2015 | A | NR |
Daryl DeGrange
|
|
|
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams Not ready for final at this time.
|
Electrical Rough-In | 7/31/2015 | 7/31/2015 | 7/31/2015 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams correction done, rough-in ok cover ceiling grid
|
Electrical Rough-In | 7/27/2015 | 7/28/2015 | 7/27/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams 210.62- Show window receptacle outlets shall be installed. Existing sign cord shall not be above grid as per 400.8 300.11- Exit sign boxes shall be supported independant of grid. 330.40- Large box above west wall connector installation not complete.
|
Electrical Rough-In | 7/22/2015 | 7/23/2015 | 7/23/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Bath and offices walls and hardlid rough in ok cover
|
Electrical Rough-In | 6/4/2015 | 6/4/2015 | 6/4/2015 | P | PART |
Rock A. Hudson
|
|
|
Ceiling Phone #: ###-#### Inspection requested via web by Jim Williams Grid not ready. Back bathroom walls and hard lid only rough in ok cover
|
Electrical Rough-In | 5/26/2015 | 5/27/2015 | 5/27/2015 | P | PASS |
Rock A. Hudson
|
|
|
Underground Phone #: ###-#### Inspection requested via web by Jim Williams Underground located in waiting area from east wall out 10 ft for new counter. Rough in ok cover
|