Final | 6/3/2015 | 6/3/2015 | 6/3/2015 | A | PASS |
Rex Boyles
|
|
|
Call for access code Range is factory hard wired without a ground, A/C is a in house unit so the extras wire in conduit runs to a branch circuit in the living room. Phone #: ###-#### Inspection requested via web by David Nelson UNIT 1- corrections made final ok
|
Rough-In Permanent Service | 6/1/2015 | 6/2/2015 | 6/2/2015 | A | CANC |
Rex Boyles
|
|
|
UNIT #1, replace panel due to flooding Phone #: ###-#### Inspection requested via web by David Nelson needed r/i only
|
Electrical Rough-In | 6/2/2015 | 6/2/2015 | 6/2/2015 | P | FAIL |
Rex Boyles
|
|
|
UNIT #1, replace panel due to flooding Phone #: ###-#### Inspection requested via web by David Nelson multi wire branch circuit needs 2 pole cir, breaker, one conduit has 3 current carrying conductors with 1 nuetral in 1 phase system, locknuts need to be tight and some need reducing washers and some with no ground conductor need tighteneing to confirm ground, strap conduits entering panel, AFCI protection to bdrms if possible, change range receptacle to 4 wire type fed from sub panel.
|