Permit Information
Permit NumberELE15-01617
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 1173 W UNIVERSITY DR
Project Name 
Customer Number575
ePlanReviewNo
Description
New: Electrical for 4 story structure
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/6/201610/7/201610/7/2016APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Items as noted ok, Final ok signed inspection record for final
Final9/29/20169/30/20169/30/2016APART
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Needed to trim out recep desk, WR GFCI's in front planter, Fire caulk penetrations in elec rooms, make handles for the Spare transformer disc on bus duct.
Electrical Rough-In9/29/20169/30/20169/29/2016ACANC
DetailsJames Ady
1st Floor Final Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
Electrical Rough-In9/23/20169/26/20169/26/2016APASS
DetailsJames Ady
1st Floor Recept Desk Phone #: ###-#### Inspection requested via web by Kerri Hamilton Reception desk and west hall adn storage ceiling first floor ok to cover
Final9/7/20169/7/20169/7/2016PCANC
DetailsJames Ady
Partial final on Floors 2,3 ; 4 Phone #: ###-#### Inspection requested via web by Kerri Hamilton Needed rough in to move furniture in
Electrical Rough-In9/7/20169/7/20169/7/2016PPASS
DetailsJames Ady
Partial final on Floors 2,3 ; 4 Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ok to move in furniture on floors 2,3 and 4 only
Electrical Rough-In9/6/20169/6/20169/6/2016PPASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough-in ok cover first floor ceiling grid areas highlighted blue and dated 9/06/16
Electrical Rough-In8/15/20168/16/20168/16/2016APASS
DetailsEric Story
1st Floor Cover Phone #: ###-#### Inspection requested via web by Kerri Hamilton
entry vestibule drop ceiling only ok cover
Electrical Rough-In8/15/20168/15/20168/15/2016PPASS
DetailsBob Reichert
2nd Floor Ceiling cover Phone #: ###-#### Inspection requested via web by Kerri Hamilton clouds ok to cover, saw from 1st floor, west side, about 4 sets
Electrical Rough-In8/11/20168/12/20168/12/2016ANH
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Called contact no answer left message. Must Recall
Electrical Rough-In8/2/20168/3/20168/3/2016PPASS
DetailsJames Ady
4th floor ceiling cover. Thanks Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling ok to cover as marked on print
Electrical Rough-In8/1/20168/2/20168/2/2016PPART
DetailsJames Ady
4th floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling as marked on contractor print ok to cover
Electrical Rough-In7/29/20168/1/20168/1/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Parking lot planter underground rough in ok cover
Electrical Rough-In7/27/20167/28/20167/28/2016APASS
DetailsEric Story
Cover 2nd ; 3rd Floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton
areas noted on contractors print, suspended ceilings only ok cover
Electrical Rough-In7/27/20167/27/20167/27/2016PPASS
DetailsEric Story
Cover, 1st floor Ball Room Phone #: ###-#### Inspection requested via web by Kerri Hamilton
ballroom columns only ok cover
Electrical Rough-In7/21/20167/22/20167/22/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
1st floor soffits and bath foyer lids rough in ok cover
Electrical Rough-In7/14/20167/15/20167/15/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Underground in planters in south parking lot rough in ok cover
Electrical Rough-In7/13/20167/14/20167/14/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Living area soffits and columns rough in ok cover
Electrical Rough-In7/12/20167/12/20167/12/2016PPASS
DetailsEric Story
ug Phone #: ###-#### Inspection requested via web by Kerri Hamilton
south entrance area for planters u/g ok cover
Electrical Rough-In7/7/20167/8/20167/8/2016APASS
DetailsDaryl DeGrange
Underground. 3 raised planters on north side of building
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough-in ok cover
Electrical Rough-In6/30/20166/30/20166/30/2016PPASS
DetailsJames Ady
Ceiling Phone #: ###-#### Inspection requested via web by Kerri Hamilton 1 room 2nd floor 3 rooms 3rd floor, all marked on contractor print. Ceiling Rough in ok to cover
Electrical Rough-In6/23/20166/27/20166/27/2016APASS
DetailsRock A. Hudson
Ceiling rough-in for 2nd and 3rd floors Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Grid as noted on contractor print in blue rough in ok cover
Electrical Rough-In6/23/20166/24/20166/24/2016APASS
DetailsRock A. Hudson
Elevator cover for 2nd, 3rd, and 4th floors Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Elevator door wall rough in ok cover as noted
Electrical Rough-In6/13/20166/14/20166/14/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
1st floor entry soffits and east fireplace wall, 4th floor student desk soffit and bathroom hardlids rough in ok cover
Electrical Rough-In6/7/20166/7/20166/7/2016PPASS
DetailsRock A. Hudson
Underground Phone #: ###-#### Inspection requested via web by Kerri Hamilton
South parking lot east 1/2 underground rough in ok cover
Electrical Rough-In6/6/20166/6/20166/6/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
4 pole bases north side and east 1 rough in ok cover
Electrical Rough-In6/3/20166/3/20166/3/2016PPASS
DetailsRock A. Hudson
Cover Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Underground south east corner of building and 2nd and 3rd floor conference room soffit cans rough in ok cover
Electrical Rough-In5/31/20165/31/20165/31/2016PPASS
DetailsRock A. Hudson
Underground Phone #: ###-#### Inspection requested via web by Kerri Hamilton
North side from center of building to planter and under sidewalk rough in ok cover.
Electrical Rough-In5/26/20165/26/20165/26/2016PPASS
DetailsJames Ady
Underground Phone #: ###-#### Inspection requested via web by Kerri Hamilton SW corner ok to cover
Electrical Rough-In5/24/20165/25/20165/25/2016PPASS
DetailsJames Ady
Underground
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Underground ok to cover SE corner only
Electrical Rough-In5/24/20165/25/20165/25/2016APASS
DetailsRock A. Hudson
Underground
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Parking lot underground 2 east trenches and 4 interior pole bases rough in ok cover. Discussed travel areas in parking area ok to cover trenches prior to inspection if photos are taken.
Electrical Rough-In5/19/20165/20/20165/20/2016PPASS
DetailsRock A. Hudson
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Pole bases around south parking lot 8 total rough in ok cover
Electrical Rough-In5/17/20165/18/20165/18/2016APASS
DetailsRock A. Hudson
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Underground west side of bldg to S.W corner for pole bases rough in ok cover
Permanent Service5/12/20165/13/20165/13/2016APASS
DetailsRex Boyles
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton p/s u/g n ok NOT:already energized (customer owned) Ron will keep everything locked out and doors will be installed on main electrical room and all other electrical rooms throughout project. Will look for waterbond and sprinkeler riser bond at next inspection
Electrical Rough-In5/12/20165/13/20165/13/2016APASS
DetailsRex Boyles
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok stairwell 1 hard lid and walls on all floors in stairwell 1
Electrical Rough-In5/11/20165/11/20165/11/2016PPASS
DetailsRex Boyles
Cover
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok 4 north interior columns
Electrical Rough-In4/25/20164/26/20164/26/2016APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok 2 ballroom columns, 2nd floor bathrooms ceilings,, 3rd floor womens bathroom ceiling
Conference4/1/20164/4/20164/4/2016PDONE
DetailsRex Boyles
Ron Hamilton
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discuss data backboard install above xformer on each floor. OK to do this
Electrical Rough-In3/23/20163/24/20163/24/2016APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok entire north exterior wall (living rm. wall)
Electrical Rough-In3/17/20163/18/20163/18/2016APASS
DetailsRex Boyles
1st Floor Exterior Soffit Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok all soffit recessed lights except front area
Electrical Rough-In2/26/20162/29/20162/29/2016APASS
DetailsRex Boyles
Cover inspection for 1st Floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok walls on 1st floor BUT NO SOFFITS, r/i ok walls 4th floor
Electrical Rough-In2/8/20162/8/20162/8/2016PPASS
DetailsRex Boyles
Ron Hamilton
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i all walls ok on 2nd and 3rd floors
Conference1/5/20161/6/20161/6/2016ADONE
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton walk thru and look at HVAC air handeler VAV units for clearance issues. After walk thru clearances look ok. No problems at this time.
Electrical Rough-In1/5/20161/6/20161/6/2016APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i walls in electrical, mechanical and data rooms as per notes on sheets E2.1P, E2.2P and E2.3P
Conference11/16/201511/17/201511/17/2015ADONE
DetailsDaryl DeGrange
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton NEC 110.26(C) Discuss adequate accessibility to service gear install parapet wall for rooftop units.
Electrical Rough-In10/13/201510/14/201510/14/2015APASS
DetailsRex Boyles
Marcelo Leon Phone #: ###-#### Inspection requested via web by Kerri Hamilton 4 front columns r/i ok
Conference8/24/20158/25/20158/25/2015ADONE
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discuss clearances for electrical panels in air handelers as per 110.26(A)(1). Need 3' 6" for the 277 voltage in front of units and approx. 30" wide clearance. Exceptions for side panels to replace filters and blower motors where limited.
Electrical Rough-In7/17/20157/20/20157/20/2015APASS
DetailsDaryl DeGrange
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough-in ok cover underground, N.W area or Ballroom
Electrical Rough-In7/15/20157/16/20157/16/2015APASS
DetailsRex Boyles
Ron Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok underslab conduits from main electric rm. to the east electric rm.
Electrical Rough-In7/8/20157/9/20157/9/2015PPASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i under slab conduits from 6 line to the east ok . Also underground conduits from front of bldg. to columns ok
Electrical Rough-In7/1/20157/2/20157/2/2015APASS
DetailsRex Boyles
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton r/i ok remainder of telco underground
Electrical Rough-In6/22/20156/23/20156/23/2015APASS
DetailsRex Boyles
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton grounding electrode ok and 4-front column stub outs ok
Electrical Rough-In6/16/20156/16/20156/16/2015PPASS
DetailsDaryl DeGrange
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough-in ok cover underground service feeders to location of stub-ups
Electrical Rough-In6/4/20156/5/20156/5/2015APASS
DetailsRex Boyles
Ron Hamilton Phone #: ###-#### Inspection requested via web by Kerri Hamilton xformer pad to electric rm. u. ground ok. Discuss routing of fire pump conduit engineered incorrectly on single line diagram.
Electrical Rough-In6/3/20156/4/20156/4/2015APASS
DetailsRex Boyles
Phone #: ###-#### Inspection requested via web by Kerri Hamilton continue primarys to xformer pad ok
Electrical Rough-In6/2/20156/2/20156/3/2015PPASS
DetailsRex Boyles
Underground Phone #: ###-#### Inspection requested via web by Kerri Hamilton u. ground 12.500 volt primary and fiber optic conduits ok to cover across Grant street