Final | 12/11/2015 | 12/11/2015 | 12/11/2015 | P | PASS |
Bob Reichert
|
|
|
Rick- Phone #: ###-#### corrections made, ok final
|
Final | 12/1/2015 | 12/2/2015 | 12/2/2015 | A | FAIL |
Rex Boyles
|
|
|
Richard Phone #: ###-#### guy kit still needs to be installed, NEC 406.9- all exterior receptacles shall be weather resistant and have in extra duty in use covers. 422.16(B)(4)(4)-range hood shall have lockoff on circuit breaker if receptacle is not readily accessable or hard wired. Also identify hood in panel schedule
|
Final | 11/20/2015 | 11/23/2015 | 11/23/2015 | A | CANC |
Bob Reichert
|
|
|
Rick Phone #: ###-#### see p/s
|
Permanent Service | 11/23/2015 | 11/23/2015 | 11/23/2015 | A | PASS |
Bob Reichert
|
|
|
Rick Phone #: ###-#### check for guy kit at final, p/s o/h rec ok
|
Electrical Rough-In | 9/2/2015 | 9/3/2015 | 9/3/2015 | A | PASS |
Bob Reichert
|
|
|
Rick Phone #: ###-#### corrections made, ri ok
|
Electrical Rough-In | 8/31/2015 | 8/31/2015 | 8/31/2015 | P | FAIL |
Eric Story
|
|
|
Rick-would like inspection after 3:30. works until 3:15-please call if this doens''t work Phone #: ###-#### 300.4 bored holes 1 1/4 shall be protected from physical damage-210.52 wall spacing shall have a receptacle on walls greater then 2' and no more then 6'- 4-05-31 BCO no unfused conductors allow in a structure
|
Conference | 6/16/2015 | 6/16/2015 | 6/16/2015 | P | DONE |
Bob Reichert
|
|
|
Paul Phone #: ###-#### talked about t/s, getting new permit, owner only do work, not freinds, NEC and items to follow
|