Final | 7/10/2015 | 7/13/2015 | 7/13/2015 | P | PASS |
Bob Reichert
|
|
|
Inspection requested via web by shane miller corrections made, ok final
|
Final | 7/7/2015 | 7/8/2015 | 7/8/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller Overcurrent device over ampacity of subpanel feeders, Need to strap service raiser, NEC 408.41Terminate one neutral conductor per lug. Provide equipment grounding conductor for A/C branch circuit, Secure branch circuits at subpanel within 12in.
|
Rough-In Permanent Service | 7/2/2015 | 7/7/2015 | 7/7/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller verify water bond on final rough-in ok p/s o/h n rec ok
|