Final | 7/8/2015 | 7/9/2015 | 7/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Please call prior to inspection for access Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
Electrical Rough-In | 7/8/2015 | 7/9/2015 | 7/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Please call prior to inspection for access Phone #: ###-#### Inspection requested via web by kendall bender Corrections done. Rough in ok
|
Final | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender See rough in
|
Electrical Rough-In | 7/7/2015 | 7/7/2015 | 7/7/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Please call for access Phone #: ###-#### Inspection requested via web by kendall bender 110.14- Dissimilar metals shall not be in physical contact with each other in connnector. 422.30- A disconnecting means shall be provided for furnace with in sight of unit. Verbal with contact.
|