Final | 8/12/2015 | 8/13/2015 | 8/13/2015 | A | PASS |
Rock A. Hudson
|
|
|
Gate is open thanks MIke Phone #: ###-#### Inspection requested via web by michael hunt Scope of work changed to future underground and sub panel with 1 general purpose receptacle outlet. Final ok
|
Final | 8/12/2015 | 8/12/2015 | 8/12/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Side gate open, back garage door unlocked. No pets. Not wiring greenhouse only new sub panel with 120v. Outlet. Thanks Mike Phone #: ###-#### Inspection requested via web by michael hunt 406.12- All 15 or 20 amp 120 volt receptacle outlets installed in or on a residence shall be tamper resistant type
|
Electrical Rough-In | 7/8/2015 | 7/9/2015 | 7/9/2015 | A | PASS |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Contractor called hot tub is a portable unit and location has not been determined. Location marked on ground 7-8-15 underground has been routed around this area. Underground rough in ok cover
|
Electrical Rough-In | 7/7/2015 | 7/8/2015 | 7/8/2015 | P | FAIL |
Rock A. Hudson
|
|
|
conduit inspection prior to being under concrete. Phone #: ###-#### Inspection requested via web by michael hunt 680.10- Underground wiring not associated with pool or hot tub shall not be installed with in 5' horizontal from waters edge.
|