Final | 7/20/2015 | 7/21/2015 | 7/21/2015 | P | PASS |
Bob Reichert
|
|
|
The homeowner is able to be home from 4 pm to 5 pm, for inspection. call ahead to verify that window at 272.3277 or 340.7376
10 solar panels. AC micro-inverter system. No DC voltage. Enphase M250 Micro-Inverters, that are CSA, IEEE-1547, and UL-1741 listed. Ironridge Integrated Grounding System mid clamps, bonding straps and bonding lugs. And 275 watt Suniva panels, ETL listed.
A single home run, in metal conduit, is ran from the solar array to the knife switch, located next to meter base. From the knife switch to breaker in main panel, at the bottom of the busing, opposite the feeder lugs. The solar breaker and the knife switch are permanently marked for solar, and the circuit numbers identified in the knife switch and on the panel schedule.
The inverters, panels and rails are all bonded with a number 6 ground that runs back to the service grounding electrode lug at the top of the main panel. Phone #: ###-#### Inspection requested via web by Ryan King ok final
|
Electrical Rough-In | 7/15/2015 | 7/16/2015 | 7/16/2015 | A | PASS |
Bob Reichert
|
|
|
The panel crew will arrive between 9 and 10 depending on load up time, and will be there all afternoon. Phone #: ###-#### Inspection requested via web by Ryan King equipment is listed, ri ok
|