Final | 10/5/2015 | 10/5/2015 | 10/5/2015 | A | PASS |
Eric Story
|
|
|
All corrections have been made. Please call half an hour before inspection to insure access. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman corrections made final ok
|
Final | 10/1/2015 | 10/2/2015 | 10/2/2015 | A | FAIL |
Eric Story
|
|
|
Please call if you have any questions. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman 210.8 (6)@(5) GFCI protection required for kitchen receptacles and receptacles located within 6' of a sink 410.10 (a) luminaires installed in a wet locations shall indentified for a wet location reverse polarity in multiple receptacles in unit
|
Electrical Rough-In | 7/21/2015 | 7/21/2015 | 7/21/2015 | A | PASS |
Bob Reichert
|
|
|
Lock box code is 7828 Phone #: ###-#### Inspection requested via web by Shaun Kirkman ri ok lighting and bath
|