Final | 2/12/2018 | 2/12/2018 | 2/12/2018 | P | PASS |
Tom Saunders
|
|
|
to close permit...structure has been torn down
|
Permanent Service | 7/21/2015 | 7/22/2015 | 7/22/2015 | A | PASS |
Daryl DeGrange
|
|
|
Jon Fivecoat is contact at ###-####..thank ou Phone #: ###-#### Inspection requested via web by Debby Pierce Additional ground rod needed for final NEC 250.56 p/s o/h rec ok
|
Final | 7/21/2015 | 7/21/2015 | 7/21/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Contact is Jon Fivecoat at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce See permenant service.
|
Permanent Service | 7/21/2015 | 7/21/2015 | 7/21/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Contact is Jon Fivecoat at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce BCC 4-05-32- Code violations not to be retained. 200.6- Grounded conductor shall be identified with white. 250.50- All available grounding electode systems shall be used. Metal water pipe. 250.134-Concentic broken out in bot of panel. Shall be repaired. 230.24-Overhead service mast shall be secured in place.
|