Final | 9/17/2015 | 9/17/2015 | 9/17/2015 | P | PASS |
Eric Story
|
|
|
Garage code 0500 Phone #: ###-#### Inspection requested via web by daniel bibikov final ok
|
Permanent Service | 8/26/2015 | 8/26/2015 | 8/26/2015 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov p/s u/g n ok
|
Final | 7/24/2015 | 7/24/2015 | 7/24/2015 | P | CANC |
Rock A. Hudson
|
|
|
Rough in only Phone #: ###-#### Inspection requested via web by daniel bibikov Needed a rough in inspection
|
Electrical Rough-In | 7/24/2015 | 7/24/2015 | 7/24/2015 | P | PASS |
Rock A. Hudson
|
|
|
Rough in only Phone #: ###-#### Inspection requested via web by daniel bibikov Corrections remain on service underground. Rough in ok cover
|
Rough-In Permanent Service | 7/23/2015 | 7/23/2015 | 7/23/2015 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 300.4- NM cable ran through bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage. powder and under stair. 300.5- Under ground conduit shall be a minimum of 18" deep. 352.48- Joint at expansion joint and 90 degree elbow not square so cannot be seeded in very well. Already separating.
|