Final | 12/11/2015 | 12/11/2015 | 12/11/2015 | P | PASS |
Eric Story
|
|
|
Garage code is 6767 Phone #: ###-#### Inspection requested via web by TOM BICANDIfinal ok
|
Rough-In Permanent Service | 7/27/2015 | 7/27/2015 | 7/27/2015 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 7/24/2015 | 7/27/2015 | 7/27/2015 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 250.24(A)- Grounded service shall have a grounding electrode installed. Unable to locate concrete encased. 300.4- Nail plates needed in room back of garage in corner and SER in kitchen area. All WUI zone soffit lights are 2 gang 2 hour fire rated boxes OK OK to foam seal
|