Final | 11/19/2015 | 11/19/2015 | 11/19/2015 | P | PASS |
Eric Story
|
|
|
corrections fixed final ok
|
Final | 11/13/2015 | 11/13/2015 | 11/13/2015 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 210.8(5)unfinished basements all 120V receptacles shall haveGFCI protection 210.12(a) bedrooms in a dwelling shall have AFCI protection(master bed has GFCI) 422.31 permanently installed appliances shall have means of lock out(dishwasher not set) 406.6 faceplates required (kitchen)
|
Electrical Rough-In | 7/30/2015 | 7/30/2015 | 7/30/2015 | A | PASS |
Rex Boyles
|
|
|
Please call 30 minutes prior ###-#### Phone #: ###-#### Inspection requested via web by John VanZandt r/i ok p/s u/g n ok
|
Electrical Rough-In | 7/30/2015 | 7/30/2015 | 7/30/2015 | A | CANC |
Eric Story
|
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Inspection cancelled from web by: John VanZandt
|