Final | 10/27/2015 | 10/28/2015 | 10/28/2015 | A | PASS |
Eric Story
|
|
|
Key in outlet by front door Phone #: ###-#### Inspection requested via web by danny perrine final ok
|
Rough-In Permanent Service | 8/20/2015 | 8/21/2015 | 8/21/2015 | A | PASS |
Eric Story
|
|
|
key on back tire of triailer Phone #: ###-#### Inspection requested via web by danny perrine rough-in ok cover p/s o/h n ok
|
Rough-In Permanent Service | 8/19/2015 | 8/20/2015 | 8/20/2015 | A | FAIL |
Eric Story
|
|
|
Key on back tire of trailer Phone #: ###-#### Inspection requested via web by danny perriner 300.4 bored holes through wood members shall ne protected from physical damage-300.4 insulated fittings required for conductors larger then #4-334.30 securing and supporting of type nm cable shall be supported with 12" of a box
|
Conference | 7/30/2015 | 7/30/2015 | 7/30/2015 | P | DONE |
Eric Story
|
|
|
Like to have you check out the wellhead that will be in the concrete floor of the shop. Please call when on site to discuss ###-#### Danny Phone #: ###-#### Inspection requested via web by danny perrine conference on running u/f through chase for well controller
|