Final | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | PASS |
James Ady
|
|
|
Vince Phone #: ###-#### Corrections made final ok
|
Final | 7/20/2016 | 7/21/2016 | 7/21/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Vince Phone #: ###-#### 210.8- All outdoor 120 volt receptacle outlets shall have GFCI protection. 210.8- All 120 volt receptacle outlets located in garage shall have GFCI protection. 210.11(C)-Bathroom receptacles shall be fed by a dedicated 20 amp circuit that shall have no other outlets.
|
Electrical Rough-In | 11/23/2015 | 11/24/2015 | 11/24/2015 | P | PASS |
Rex Boyles
|
|
|
Walter Phone #: ###-#### r/i ok add 2 recpt. to bdrm. to satisfy spacing
|
Electrical Rough-In | 11/18/2015 | 11/19/2015 | 11/19/2015 | A | PASS |
Rex Boyles
|
|
|
Vince Phone #: ###-#### r/i ok wall behind furnace ok to cover
|
Conference | 10/26/2015 | 10/27/2015 | 10/27/2015 | P | DONE |
Rex Boyles
|
|
|
Vince Phone #: ###-#### discuss residential codes for addition . sub panel being installed in "hot" wall needs fire barrier. They will confirm with bldg. inspector . discuss recep. spacing, circuits required, Keep dedicated circuit to garage, bathroom arc fault for bdrm, etc
|