Final | 9/30/2015 | 10/1/2015 | 10/1/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a final inspection for tomorrow 10/1 in the early Am if possible. Our contact is Luke @ ###-#### or Todd @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Contractor repaired all open wiring and plug strips that he could find above grid for comera locations. Final ok
|
Electrical Rough-In | 9/28/2015 | 9/29/2015 | 9/28/2015 | A | CANC |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection tomorrow 9/29/15 in the early AM if possible. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
|
Electrical Rough-In | 9/23/2015 | 9/24/2015 | 9/24/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a partial final for the customer service area for tomorrow morning 9/24/15 in the AM between 7am and 8:30am. Our contact is Luke @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate Ok to occupy customer service area. Temp final ok
|
Final | 9/22/2015 | 9/22/2015 | 9/22/2015 | P | PART |
Rock A. Hudson
|
|
|
Need pertial final for fitting rooms. ###-#### Final for fitting rooms ok
|
Electrical Rough-In | 9/17/2015 | 9/18/2015 | 9/18/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection in the customer service area for Friday 9/18/15 in the AM. Our contact for this is Todd @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rough in ok cover
|
Electrical Rough-In | 9/15/2015 | 9/15/2015 | 9/15/2015 | P | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in inspection in the fitting rooms. Our contact is Todd @###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rough in ok cover
|
Electrical Rough-In | 9/3/2015 | 9/4/2015 | 9/4/2015 | A | CANC |
Daryl DeGrange
|
|
|
We are requesting a partial final inspection in the snack area for tomorrow 8/4/15 in the early AM between 7:30am -8:30am if possible. Our onsite contact is Luke @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate
|
Final | 9/4/2015 | 9/4/2015 | 9/4/2015 | P | PART |
Daryl DeGrange
|
|
|
We are requesting a partial final inspection in the snack area for tomorrow 8/4/15 in the early AM between 7:30am -8:30am if possible. Our onsite contact is Luke @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate Plug strip through ceiling grid powers security cameras, code voilation addressed at time of ceiling grid inspection Partial final for snack bar area only
|
Electrical Rough-In | 9/2/2015 | 9/3/2015 | 9/3/2015 | A | FAIL |
Daryl DeGrange
|
|
|
We are requesting an rough-in inspection for tomorrow 8/3/15 in the early am. Could the inspector please call our PM Todd Hall at ###-#### when he is in route. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate NEC 400.8 still remains, Flexible cord through ceiling grid. BCC 4-05-32 No code voilation shall be retained. NEC 210.8(5) sinks, All 15 and 20 ampere 120 volt receptacles within 6 ft. of the ouside edge of a sink shall have GFCI protection.
|
Conference | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | DONE |
Rock A. Hudson
|
|
|
We are requesting a consult for tomorrow morning 8/27/15. Our onsite contact is Luke @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate BCC 4-05-32- Code Violation not to be retained. Contractor reported open splices and flexible cords and data cables ran through out intire store area above grid. NEC 300.15-Boxes where required. Conduit or cable a box shall be installed at each conductor splice point. NEC 300.11- All wiring and cables shall not be secured to or supported by the ceiling assembly. Grandfathered in OK. NEC 400.8- Flexible cords shall not be ran through holes in structural ceiling or ren above structural ceiling. All extension cords, or plug strips located above grid shall be removed.
|
Electrical Rough-In | 8/24/2015 | 8/25/2015 | 8/25/2015 | A | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough in inspection for tomorrow morning -early AM if possible. Our onsite contact is Luke ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Wall rough in ok cover
|
Electrical Rough-In | 8/25/2015 | 8/25/2015 | 8/25/2015 | P | FAIL |
Rock A. Hudson
|
|
|
We are requesting a wall rough in inspection for tomorrow morning -early AM if possible. Our onsite contact is Luke ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Ceiling to remain the same however BCC 4-05-32 Code violations not to be retained. 300.11- All wiring and cables shall not be secured to or supported be the ceiling assembly. All communication cables shall be supported independant of grid. 400.8- Flexible cords shall not be run through holes in structural ceiling or run above structural ceiling. Power strip plugged into receptacle, run through hole and laying on grid shall be removed.
|
Electrical Rough-In | 8/17/2015 | 8/17/2015 | 8/17/2015 | P | PASS |
Rock A. Hudson
|
|
|
underground; Todd Phone #: ###-#### Under slab in jewelry area rough in ok cover
|